Concealed type Sprinkler (Standard Response)
NewAge Concealed Type Sprinkler, Standard Response – flush ceiling cover plate, 57°C plate drop + 68°C head activation, 22 GPM, UL Listed.
Description
The NewAge Concealed Type Sprinkler (Standard Response) hides above a flush ceiling cover plate for architectural discretion, unlike the visible Pendent, Upright, and Sidewall types. A fusible metal (about 60% Tin alloy) cover plate drops away at 57°C, exposing the sprinkler head, which then activates at its own 68°C nominal rating – a two-stage response built into the concealed design. Requires a 60-70mm diameter hole in the ceiling for installation. Discharge rate 22 GPM. Made of Bronze, K Factor 5.6 (80), 1/2″ NPT or 1/2″ PT connection, UL Listed, Chrome finish. Rated for 175 PSI (12.3 Kg/cm2) maximum working pressure. Jaideo Automation supplies NewAge fire protection equipment across India – contact us with your project requirements for a quotation.